DOE/EPRI National Database Repository of Power System Events


Disturbance Library Home




Use the dropdown to filter by site name. Click the EventId to see event waveforms and download data.

EventId SiteName FeederId Phase First Event Last Event Cause Weather Isolation Equipment Code Failed Equipment Code Details
0001 Site0009 F_0000065 2 2005-01-01 10:10:34.487 2005-01-01 10:10:39.870 Tree Clear Weather Recloser LINE CUT Fault caused line recloser lockout. Tree Outside Right of Way (Fall/Lean On Primary)
0004 Site0009 F_0000065 2 2005-01-01 10:10:34.487 2005-01-01 10:10:39.870 Tree Clear Weather Recloser LINE CUT Fault caused line recloser lockout. Tree Outside Right of Way (Fall/Lean On Primary)
0005 Site0009 F_0000065 2 2005-01-01 10:10:34.487 2005-01-01 10:10:39.870 Tree Clear Weather Recloser LINE CUT Fault caused line recloser lockout. Tree Outside Right of Way (Fall/Lean On Primary)
0007 Site0009 F_0000065 2 2005-01-01 10:10:34.487 2005-01-01 10:10:39.870 Tree Clear Weather Recloser LINE CUT Fault caused line recloser lockout. Tree Outside Right of Way (Fall/Lean On Primary)
3042 Site0006 F_0000041 4 2005-01-04 03:39:06.000 2005-01-04 03:39:06.000 Equipment Unknown Fuse Other Equipment, Device UG, Damaged.
0021 Site0009 F_0000061 1 2005-01-07 19:20:10.599 2005-01-07 19:20:10.613 Equipment Clear Weather CO15 FUSE Overhead Insulator Failure. BROKEN INSULATOR
0022 Site0009 F_0000061 1 2005-01-07 19:20:10.599 2005-01-07 19:20:10.613 Equipment Clear Weather Fuse CO15 FUSE Overhead Insulator Failure. BROKEN INSULATOR
0062 Site0009 F_0000065 4 2005-01-14 05:39:59.364 2005-01-14 05:40:01.198 Undetermined Raining CO15LB FUSE storm
0064 Site0009 F_0000065 4 2005-01-14 05:39:59.364 2005-01-14 05:40:01.198 Undetermined Raining CO15LB FUSE storm
0067 Site0009 F_0000065 4 2005-01-14 07:22:52.495 2005-01-14 07:22:52.828 Tree Thunderstorm CO15LB FUSE Tree/Limb Growth
0065 Site0009 F_0000065 4 2005-01-14 07:22:52.495 2005-01-14 07:22:52.828 Tree Thunderstorm CO15LB FUSE Tree/Limb Growth
0068 Site0009 F_0000065 2 2005-01-14 08:07:18.573 2005-01-14 08:07:18.573 Tree Clear Weather   CUSTOMER VINES ON TRANSFORMER
2760 Site0010   1 2005-01-18 05:41:21.000 2005-01-18 05:41:21.000 Unknown Unknown Unknown Unknown Short duration variation. No outage information found.
3048 Site0012 F_0000037 3 2005-01-25 03:29:36.000 2005-01-25 03:29:51.000 Equipment Unknown Breaker Capacitor Equipment, Capacitor Station, Damaged.
2761 Site0010 F_0000032 4 2005-01-30 16:02:34.000 2005-01-30 16:02:34.000 Equipment   Breaker   A conductor off the pin on the mainline of F_0000032 out of Site0010 Sub caused the circuit breaker to trip.
2762 Site0010 F_0000029 2 2005-02-02 15:10:14.000 2005-02-02 15:10:14.000 Equipment   Breaker   A cable fault on the underground portion of F_0000029 out of Site0010 Sub. caused the circuit breaker to trip.
3067 Site0006 F_0000041 2 2005-02-11 06:10:46.000 2005-02-11 06:10:46.000 Weather Wind Breaker No Damage Undetermined, Wind / Weather Related.
0207 Site0009 F_0000062 4 2005-02-28 07:49:04.979 2005-02-28 07:49:04.979 Undetermined Snow/Ice CO15LB FUSE snow on limbs into lines
2765 Site0010 F_0000022 2 2005-03-05 13:21:43.000 2005-03-05 13:21:43.000 Equipment   Breaker   A cable fault on the underground portion of F_0000022 out of Site0010 Substation tripped the circuit breaker.
0249 Site0009 F_0000065 4 2005-03-08 13:06:09.670 2005-03-08 13:06:16.919 Tree Major Storm CO15 FUSE Tree Outside Right of Way (Fall/Lean On Primary). Tree fell on phase A.
0247 Site0009 F_0000065 4 2005-03-08 13:06:09.670 2005-03-08 13:06:16.919 Tree Major Storm CO15 FUSE Tree Outside Right of Way (Fall/Lean On Primary). Tree fell on phase A.
0245 Site0009 F_0000065 4 2005-03-08 13:06:09.670 2005-03-08 13:06:16.919 Tree Major Storm CO15 FUSE Tree Outside Right of Way (Fall/Lean On Primary). Tree fell on phase A.
0243 Site0009 F_0000065 4 2005-03-08 13:06:09.670 2005-03-08 13:06:16.919 Tree Major Storm CO15 FUSE Tree Outside Right of Way (Fall/Lean On Primary). Tree fell on phase A.
0251 Site0009 F_0000065 1 2005-03-08 13:28:22.677 2005-03-08 13:28:22.677 Tree Major Storm   CUSTOMER Tree Outside Right of Way (Fall/Lean On Primary). Tore primary line down.
0253 Site0009 F_0000063 1 2005-03-08 14:49:09.783 2005-03-08 14:49:09.783 Tree Major Storm CO15LB FUSE Limb Fell from Outside Right of Way
0287 Site0009 F_0000061 5 2005-03-17 05:03:51.000 2005-03-17 05:04:07.900 Vehicle Snow/Ice SECT200NLB SECTIONALIZER CAR HIT POLE
0284 Site0009 F_0000061 5 2005-03-17 05:03:51.000 2005-03-17 05:04:07.900 Vehicle Snow/Ice SECT200NLB SECTIONALIZER CAR HIT POLE
0283 Site0009 F_0000061 5 2005-03-17 05:03:51.000 2005-03-17 05:04:07.900 Vehicle Snow/Ice SECT200NLB SECTIONALIZER CAR HIT POLE
0281 Site0009 F_0000061 5 2005-03-17 05:03:51.000 2005-03-17 05:04:07.900 Vehicle Snow/Ice SECT200NLB SECTIONALIZER CAR HIT POLE
0289 Site0009 F_0000061 7 2005-03-17 05:58:49.612 2005-03-17 05:58:49.612 Planned Snow/Ice OCB BREAKER/SWITCH Repair/Replace Damaged or Failed Facilities
3127 Site0012 F_0000037 2 2005-03-22 18:33:30.000 2005-03-22 18:33:30.000 Equipment Unknown Fuse Transformer Equipment, Transformer UG, Damaged.
0306 Site0009 F_0000063 1 2005-03-23 07:21:16.755 2005-03-23 07:21:18.505 Planned Clear Weather CO15 FUSE Repair/Replace Damaged or Failed Facilities
0366 Site0009 F_0000065 2 2005-03-28 07:53:48.010 2005-03-28 07:53:48.010 Equipment Thunderstorm   CUSTOMER lightning. Cutout/Fuse Link Failure
2771 Site0014 F_0000012 1 2005-04-06 15:05:06.000 2005-04-06 15:05:06.000 Equipment   Breaker   A splice failure on the aerial cable portion of F_0000012 from Site0014 Sub. caused the circuit breaker to trip.
0550 Site0009 F_0000065 2 2005-04-20 10:36:17.051 2005-04-20 10:36:17.051 Equipment Clear Weather CO15LB FUSE Fuse was blown, did not see any problems. Loggers at end of road say they did not hit line.
2776 Site0010 F_0000030 4 2005-05-06 10:01:38.000 2005-05-06 10:01:38.000 Equipment   Breaker   A cable fault on the UG lead cable portion of F_0000030 from Site0010 failed.
0713 Site0009 F_0000063 1 2005-05-12 20:51:03.016 2005-05-12 20:51:03.016 Equipment Thunderstorm CO15 FUSE Cutout/Fuse Link Failure. lighting in area
0715 Site0009 F_0000064 1 2005-05-12 20:59:47.344 2005-05-12 20:59:47.344 Undetermined Thunderstorm CO15LB FUSE  
0716 Site0009 F_0000064 1 2005-05-13 01:36:09.533 2005-05-13 01:36:09.533 Tree Thunderstorm   CUSTOMER Fuse on transformer was blown due to tree limb on trans riser. Tree/Limb Growth
0716 Site0009 F_0000064 1 2005-05-13 01:36:09.533 2005-05-13 01:36:09.533 Tree Thunderstorm   CUSTOMER Fuse on transformer was blown due to tree limb on trans riser. Tree/Limb Growth
0722 Site0009 F_0000062 4 2005-05-15 07:09:03.962 2005-05-15 07:09:04.379 Animal Clear Weather CO15LB FUSE  
0719 Site0009 F_0000062 4 2005-05-15 07:09:03.962 2005-05-15 07:09:04.379 Animal Clear Weather CO15LB FUSE  
0723 Site0009 F_0000063 1 2005-05-15 09:19:19.125 2005-05-15 09:19:19.125 Tree Clear Weather CO15 FUSE Tree Inside Right of Way (Fall/Lean On Primary)
0775 Site0009 F_0000063 2 2005-05-17 06:33:49.340 2005-05-17 06:33:49.340 Undetermined Clear Weather CO15 FUSE possible riser to close to pole
0803 Site0009 F_0000063 4 2005-05-19 04:04:11.465 2005-05-19 06:02:52.132 Equipment Clear Weather R100-4E RECLOSER Overhead Arrester Failure. UNKNOWN CAUSE AT TIME
0807 Site0009 F_0000063 4 2005-05-19 04:04:11.465 2005-05-19 06:02:52.132 Equipment Clear Weather R100-4E RECLOSER Overhead Arrester Failure. UNKNOWN CAUSE AT TIME
0804 Site0009 F_0000063 4 2005-05-19 04:04:11.465 2005-05-19 06:02:52.132 Equipment Clear Weather R100-4E RECLOSER Overhead Arrester Failure. UNKNOWN CAUSE AT TIME
0781 Site0009 F_0000063 4 2005-05-19 04:04:11.465 2005-05-19 06:02:52.132 Equipment Clear Weather R100-4E RECLOSER Overhead Arrester Failure. UNKNOWN CAUSE AT TIME
0782 Site0009 F_0000063 4 2005-05-19 04:04:11.465 2005-05-19 06:02:52.132 Equipment Clear Weather R100-4E RECLOSER Overhead Arrester Failure. UNKNOWN CAUSE AT TIME
0785 Site0009 F_0000063 4 2005-05-19 04:04:11.465 2005-05-19 06:02:52.132 Equipment Clear Weather R100-4E RECLOSER Overhead Arrester Failure. UNKNOWN CAUSE AT TIME
0788 Site0009 F_0000063 4 2005-05-19 04:04:11.465 2005-05-19 06:02:52.132 Equipment Clear Weather R100-4E RECLOSER Overhead Arrester Failure. UNKNOWN CAUSE AT TIME
0790 Site0009 F_0000063 4 2005-05-19 04:04:11.465 2005-05-19 06:02:52.132 Equipment Clear Weather R100-4E RECLOSER Overhead Arrester Failure. UNKNOWN CAUSE AT TIME
0793 Site0009 F_0000063 4 2005-05-19 04:04:11.465 2005-05-19 06:02:52.132 Equipment Clear Weather R100-4E RECLOSER Overhead Arrester Failure. UNKNOWN CAUSE AT TIME
0796 Site0009 F_0000063 4 2005-05-19 04:04:11.465 2005-05-19 06:02:52.132 Equipment Clear Weather R100-4E RECLOSER Overhead Arrester Failure. UNKNOWN CAUSE AT TIME
0799 Site0009 F_0000063 4 2005-05-19 04:04:11.465 2005-05-19 06:02:52.132 Equipment Clear Weather R100-4E RECLOSER Overhead Arrester Failure. UNKNOWN CAUSE AT TIME
0801 Site0009 F_0000063 4 2005-05-19 04:04:11.465 2005-05-19 06:02:52.132 Equipment Clear Weather R100-4E RECLOSER Overhead Arrester Failure. UNKNOWN CAUSE AT TIME
0779 Site0009 F_0000063 4 2005-05-19 04:04:11.465 2005-05-19 06:02:52.132 Equipment Clear Weather R100-4E RECLOSER Overhead Arrester Failure. UNKNOWN CAUSE AT TIME
0809 Site0009 F_0000063 4 2005-05-19 06:02:54.949 2005-05-19 06:03:25.782 Equipment Clear Weather   SERVICE TRANSFORMER Overhead Transformer Outage
0811 Site0009 F_0000063 4 2005-05-19 06:02:55.000 2005-05-19 06:03:25.782 Equipment Clear Weather   SERVICE TRANSFORMER Overhead Transformer Outage
0852 Site0009 F_0000063 2 2005-05-24 16:41:55.486 2005-05-24 16:41:55.903 Lightning Thunderstorm CO15 FUSE Lightning struck transf, burned primary down.Overhead Primary Failure (No Tree Involved)
0855 Site0009 F_0000063 2 2005-05-24 16:41:55.486 2005-05-24 16:41:55.903 Lightning Thunderstorm CO15 FUSE Lightning struck transf, burned primary down.Overhead Primary Failure (No Tree Involved)
0857 Site0009 F_0000061 1 2005-05-24 23:29:42.558 2005-05-24 23:29:43.000 Equipment Windy CO15 FUSE Cutout/Fuse Link Failure. possible lightning
0859 Site0009 F_0000061 1 2005-05-25 07:29:30.345 2005-05-25 07:29:30.345 Equipment Clear Weather CO15 FUSE Overhead Transformer Outage. Bblown tap line fuse bad transformer.
0868 Site0009 F_0000065 2 2005-05-28 08:06:21.811 2005-05-28 08:06:21.811 Tree Clear Weather R100E RECLOSER Tree/Limb Growth
0947 Site0009 F_0000065 2 2005-06-05 12:31:11.868 2005-06-05 12:31:40.001 Customer Request Clear Weather   CUSTOMER CALL BACK - Lights on.
0942 Site0009 F_0000065 2 2005-06-05 12:31:11.868 2005-06-05 12:31:40.001 Customer Request Clear Weather   CUSTOMER CALL BACK - Lights on.
0940 Site0009 F_0000065 2 2005-06-05 12:31:11.868 2005-06-05 12:31:40.001 Customer Request Clear Weather   CUSTOMER CALL BACK - Lights on.
0935 Site0009 F_0000065 2 2005-06-05 12:31:11.868 2005-06-05 12:31:40.001 Customer Request Clear Weather   CUSTOMER CALL BACK - Lights on.
0952 Site0009 F_0000065 4 2005-06-05 17:01:44.427 2005-06-05 17:01:44.427 Equipment Clear Weather CO15LB FUSE Underground Transformer Outage. Need to replace trans.
0962 Site0009 F_0000065 3 2005-06-05 22:58:58.707 2005-06-06 00:05:04.522 Animal Clear Weather R-OVR-1PT RECLOSER SNAKE
0957 Site0009 F_0000065 3 2005-06-05 22:58:58.707 2005-06-06 00:05:04.522 Animal Clear Weather R-OVR-1PT RECLOSER SNAKE
0960 Site0009 F_0000065 3 2005-06-05 22:58:58.707 2005-06-06 00:05:04.522 Animal Clear Weather R-OVR-1PT RECLOSER SNAKE
0963 Site0009 F_0000065 3 2005-06-05 22:58:58.707 2005-06-06 00:05:04.522 Animal Clear Weather R-OVR-1PT RECLOSER SNAKE
0965 Site0009 F_0000065 3 2005-06-05 22:58:58.707 2005-06-06 00:05:04.522 Animal Clear Weather R-OVR-1PT RECLOSER SNAKE
0959 Site0009 F_0000065 3 2005-06-05 22:58:58.707 2005-06-06 00:05:04.522 Animal Clear Weather R-OVR-1PT RECLOSER SNAKE
2778 Site0010 F_0000024 6 2005-06-07 15:12:33.000 2005-06-07 15:12:33.000 Equipment   Breaker   A fault on the riser splice of F_0000024 out of Site0010 tripped the breaker at the substation.
1057 Site0009 F_0000064 1 2005-06-09 12:23:23.625 2005-06-09 12:23:23.625 Equipment Clear Weather   SERVICE TRANSFORMER Overhead Transformer Outage. CAUSE NOT KNOWN
3152 Site0006 F_0000041 2 2005-06-13 18:39:58.000 2005-06-13 18:39:58.000 Equipment Unknown Fuse Transformer Equipment, Transformer UG, Damaged.
3153 Site0006 F_0000039 6 2005-06-14 11:46:21.000 2005-06-14 11:46:21.000 Vehicle Unknown Fuse Pole Motor Vehicle, Pole OH, Down.
1088 Site0009 F_0000065 1 2005-06-14 15:09:11.550 2005-06-14 15:09:11.550 Vehicle Clear Weather   CUSTOMER car hit guy wire
1089 Site0009 F_0000062 2 2005-06-14 19:20:06.146 2005-06-14 19:20:06.564 Animal Clear Weather CO15LB FUSE squirrl
1106 Site0009 F_0000061 1 2005-06-16 15:37:29.702 2005-06-16 15:37:29.702 Equipment Clear Weather CO15LB FUSE Cutout/Fuse Link Failure
1108 Site0009 F_0000061 1 2005-06-17 06:16:34.960 2005-06-17 06:16:35.343 Animal Clear Weather   SERVICE TRANSFORMER SNAKE ON LIGHTNING ARRESTER
1111 Site0009 F_0000061 1 2005-06-17 06:16:34.960 2005-06-17 06:16:35.343 Animal Clear Weather   SERVICE TRANSFORMER SNAKE ON LIGHTNING ARRESTER
3164 Site0012 F_0000037 7 2005-06-28 01:24:53.000 2005-06-28 01:25:33.000 Vehicle Unknown Breaker Pole Motor Vehicle, Pole OH, Contact.
3163 Site0012 F_0000037 7 2005-06-28 01:24:53.000 2005-06-28 01:25:33.000 Vehicle Unknown Breaker Pole Motor Vehicle, Pole OH, Contact.
3162 Site0012 F_0000037 7 2005-06-28 01:24:53.000 2005-06-28 01:25:33.000 Vehicle Unknown Breaker Pole Motor Vehicle, Pole OH, Contact.
3168 Site0012 F_0000037 7 2005-06-28 01:24:53.000 2005-06-28 01:25:33.000 Vehicle Unknown Breaker Pole Motor Vehicle, Pole OH, Contact.
3166 Site0012 F_0000037 7 2005-06-28 01:24:53.000 2005-06-28 01:25:33.000 Vehicle Unknown Breaker Pole Motor Vehicle, Pole OH, Contact.
1196 Site0009 F_0000061 4 2005-06-28 15:39:42.105 2005-06-28 15:39:42.105 Customer Request Clear Weather   CUSTOMER custmer called back light on. Customer Breaker / Equipment Failure
2784 Site0014 F_0000018 4 2005-07-14 12:25:31.000 2005-07-14 12:25:31.000 Equipment   Breaker   A terminator failure on the cable dip for the Rt. 8 over pass caused the circuit breaker of F_0000018 to trip
3189 Site0012 F_0000037 7 2005-07-16 01:25:46.000 2005-07-16 01:26:05.000 Vehicle Unknown Sectionalizer Pole Motor Vehicle, Pole OH, Damaged.
3187 Site0012 F_0000037 7 2005-07-16 01:25:46.000 2005-07-16 01:26:05.000 Vehicle Unknown Sectionalizer Pole Motor Vehicle, Pole OH, Damaged.
3186 Site0012 F_0000037 7 2005-07-16 01:25:46.000 2005-07-16 01:26:05.000 Vehicle Unknown Sectionalizer Pole Motor Vehicle, Pole OH, Damaged.
3188 Site0012 F_0000037 7 2005-07-16 01:25:46.000 2005-07-16 01:26:05.000 Vehicle Unknown Sectionalizer Pole Motor Vehicle, Pole OH, Damaged.
3235 Site0006   7 2005-07-23 04:33:08.000 2005-07-23 04:33:08.000 Unknown Unknown Unknown Unknown Unknown.
2786 Site0014   4 2005-07-27 16:55:35.000 2005-07-27 16:55:35.000 Lightning Major Storm Unknown   Lightning on the transmission system outside of Utility territory caused a SARFI70 sag at Site0010.
2787 Site0010   4 2005-07-27 16:55:35.000 2005-07-27 16:55:35.000 Lightning Major Storm Unknown   Lightning on the transmission system outside of Uutility territory caused a SARFI70 sag at Site0010.
2788 Site0014   1 2005-07-27 17:08:27.000 2005-07-27 17:08:27.000 Lightning   Breaker   Lightning on the Line
2789 Site0010   1 2005-07-27 17:08:27.000 2005-07-27 17:08:27.000 Lightning   Breaker   Lightning on the Line
2792 Site0014   2 2005-08-14 14:52:33.000 2005-08-14 14:52:33.000 Lightning Major Storm Breaker   Lightning during a major storm caused the Site0010 Line breaker to trip and reclose at the substation. There were no outages associated with this event.
2791 Site0010   2 2005-08-14 14:52:33.000 2005-08-14 14:52:33.000 Lightning Major Storm Breaker   Lightning during a major storm caused the Site0010 Line breaker to trip and reclose at the substation. There were no outages associated with this event.
3296 Site0006 F_0000041 2 2005-08-20 09:32:24.000 2005-08-20 09:32:24.000 Equipment Unknown Fuse Cable Equipment, Cable UG, Damaged. (Dig in)
2795 Site0010 F_0000022 3 2005-08-21 22:17:41.000 2005-08-21 22:17:41.000 Equipment   Breaker   A lightning arrester failure caused primary wire to fall to the ground and trip the circuit breaker.
2797 Site0010   4 2005-08-30 05:47:25.000 2005-08-30 05:47:25.000 Unknown   Unknown   Unknown Cause. No outage report was found for this event.
3298 Site0006 F_0000041 2 2005-09-05 01:35:38.000 2005-09-05 01:36:04.000 Equipment Unknown Fuse Cable Equipment, Cable UG, Damaged.
2802 Site0014   7 2005-09-17 16:20:27.000 2005-09-17 16:20:27.000 Unknown Major Storm Breaker   A fault on Transmission Line during a thunderstorm caused a SARFI 70 sag at Site0010 and Site0014 Substation.
2803 Site0010   7 2005-09-17 16:20:27.000 2005-09-17 16:20:27.000 Unknown Major Storm Breaker   A fault on Transmission Line during a thunderstorm caused a SARFI 70 sag at Site0010 and Site0014 Substation.
3326 Site0012   7 2005-09-20 00:51:18.000 2005-09-20 00:51:18.000 Unknown Lightning Unknown Unknown Unknown.
3402 Site0005   6 2005-09-26 14:17:46.000 2005-09-26 14:17:46.000 Unknown Unknown Unknown Unknown Unknown.
2811 Site0014   7 2005-09-29 09:35:31.000 2005-09-29 09:35:31.000 Unknown   Breaker   A fault caused breakers to trip and caused SARFI 70 events at Substations.
2812 Site0010   7 2005-09-29 09:35:31.000 2005-09-29 09:35:31.000 Unknown   Breaker   A fault caused breakers to trip and caused SARFI 70 events at Substations.
3403 Site0006 F_0000041 1 2005-09-30 10:31:31.279 2005-09-30 10:31:37.113 Equipment Unknown Fuse Cable Equipment, Cable UG, Dig-in.
3404 Site0006 F_0000041 2 2005-09-30 10:31:31.279 2005-09-30 10:31:37.113 Equipment Unknown Fuse Cable Equipment, Cable UG, Dig-in.
2813 Site0014   7 2005-10-08 04:57:29.000 2005-10-08 04:57:29.000 Unknown   Breaker   Unknown cause. No outage reported for this event. Short duration, possible recloser operation. Cause incoming to open at the substation due to fault current over 10,000 Amps.
3425 Site0006 F_0000041 1 2005-10-18 23:06:49.000 2005-10-18 23:07:40.000 Undetermined Unknown Sectionalizer No Damage Undetermined ? Under Investigation.
3426 Site0006 F_0000041 1 2005-10-18 23:06:49.000 2005-10-18 23:07:40.000 Undetermined Unknown Sectionalizer No Damage Undetermined ? Under Investigation.
3427 Site0006 F_0000041 1 2005-10-18 23:06:49.000 2005-10-18 23:07:40.000 Undetermined Unknown Sectionalizer No Damage Undetermined ? Under Investigation.
3428 Site0006 F_0000041 1 2005-10-18 23:25:28.000 2005-10-18 23:25:35.000 Undetermined Unknown Sectionalizer No Damage Undetermined ? Under Investigation.
3429 Site0006 F_0000041 1 2005-10-18 23:25:28.000 2005-10-18 23:25:35.000 Undetermined Unknown Sectionalizer No Damage Undetermined ? Under Investigation.
3430 Site0006 F_0000041 1 2005-10-18 23:25:28.000 2005-10-18 23:25:35.000 Undetermined Unknown Sectionalizer No Damage Undetermined ? Under Investigation.
3431 Site0006 F_0000041 1 2005-10-19 01:34:21.000 2005-10-19 01:34:21.000 Undetermined Unknown Sectionalizer No Damage Undetermined ? Under Investigation.
3432 Site0006 F_0000039 1 2005-10-19 11:37:54.000 2005-10-19 11:37:54.000 Undetermined Unknown Service Restorer No Damage Undetermined.
3433 Site0005 F_0000003 7 2005-10-20 12:19:12.000 2005-10-20 12:19:12.000 Vehicle Unknown Fuse Pole Motor Vehicle, Pole OH, Damaged.
3435 Site0006 F_0000041 1 2005-10-22 03:17:24.000 2005-10-22 03:18:17.000 Vehicle Unknown Sectionalizer Fuse Cabinet Motor Vehicle, Fuse UG, Damaged
3436 Site0006 F_0000041 1 2005-10-22 03:17:24.000 2005-10-22 03:18:17.000 Vehicle Unknown Sectionalizer Fuse Cabinet Motor Vehicle, Fuse UG, Damaged
3437 Site0006 F_0000041 1 2005-10-22 03:17:24.000 2005-10-22 03:18:17.000 Vehicle Unknown Sectionalizer Fuse Cabinet Motor Vehicle, Fuse UG, Damaged
3434 Site0006 F_0000041 1 2005-10-22 03:17:24.000 2005-10-22 03:18:17.000 Vehicle Unknown Sectionalizer Fuse Cabinet Motor Vehicle, Fuse UG, Damaged
2825 Site0010   7 2005-11-09 22:15:44.000 2005-11-09 22:15:44.000 Lightning   Breaker   Lightning outside of Utility territory on transmission line caused voltage sags across our territory.
2826 Site0014   7 2005-11-09 22:15:44.000 2005-11-09 22:15:44.000 Lightning   Breaker   Lightning outside of Utility territory on transmission line caused voltage sags across our territory.
3449 Site0011 F_0000033 5 2005-11-12 18:59:06.000 2005-11-12 18:59:06.000 Undetermined Unknown Breaker No Damage Undetermined.
2827 Site0010 F_0000024 2 2005-11-20 15:34:19.000 2005-11-20 15:34:19.000 Equipment   Breaker   A cable fault on the UG lead cable portion of F_0000024 caused the circuit breaker to trip at Site0010 Substation.
3455 Site0012 F_0000009 3 2005-12-06 08:21:51.000 2005-12-06 08:21:53.000 Equipment Unknown Fuse Cable De-Energized For Safety-Equipment, Cable UG, Dig-In.
3456 Site0012 F_0000009 3 2005-12-06 08:21:51.000 2005-12-06 08:21:53.000 Equipment Unknown Fuse Cable De-Energized For Safety-Equipment, Cable UG, Dig-In.
3460 Site0006 F_0000041 4 2005-12-10 03:13:42.000 2005-12-10 03:14:33.000 Vehicle Unknown Breaker Other Motor Vehicle, Terminator UG, Damaged.
3457 Site0006 F_0000041 4 2005-12-10 03:13:42.000 2005-12-10 03:14:33.000 Vehicle Unknown Breaker Other Motor Vehicle, Terminator UG, Damaged.
3458 Site0006 F_0000041 4 2005-12-10 03:13:42.000 2005-12-10 03:14:33.000 Vehicle Unknown Breaker Other Motor Vehicle, Terminator UG, Damaged.
3459 Site0006 F_0000041 4 2005-12-10 03:13:42.000 2005-12-10 03:14:33.000 Vehicle Unknown Breaker Other Motor Vehicle, Terminator UG, Damaged.
2828 Site0010 F_0000023 2 2005-12-18 15:19:10.000 2005-12-18 15:19:10.000 Equipment   Switch Cable Cable fault at Loc. 271 tripped a fault interrupter at Loc.260. F_0000023 out of Site0010 Substation.
3472 Site0006   3 2006-01-04 14:18:06.000 2006-01-04 14:18:06.000 Unknown Unknown Unknown Unknown Unknonw.
3473 Site0006   3 2006-01-04 14:18:06.000 2006-01-04 14:18:06.000 Unknown Unknown Unknown Unknown Unknonw.
2831 Site0014   4 2006-01-15 01:00:18.000 2006-01-15 01:00:18.000 Tree Major Storm Breaker   Possible tree contact on Transmission Line during a Major windstorm.
2830 Site0010   4 2006-01-15 01:00:18.000 2006-01-15 01:00:18.000 Tree Major Storm Breaker   Possible tree contact on Transmission Line during a Major windstorm.
3498 Site0006 F_0000041 3 2006-01-24 05:32:36.000 2006-01-24 05:32:36.000 Undetermined Wind Fuse No Damage Undeterminde, Possible High Winds.
3557 Site0006 F_0000038 3 2006-02-12 12:28:39.000 2006-02-12 12:28:51.000 Undetermined Unknown Breaker No Damage Undetermined.
3555 Site0006 F_0000038 3 2006-02-12 12:28:39.000 2006-02-12 12:28:51.000 Undetermined Unknown Breaker No Damage Undetermined.
3554 Site0006 F_0000038 3 2006-02-12 12:28:39.000 2006-02-12 12:28:51.000 Undetermined Unknown Breaker No Damage Undetermined.
3553 Site0006 F_0000038 3 2006-02-12 12:28:39.000 2006-02-12 12:28:51.000 Undetermined Unknown Breaker No Damage Undetermined.
3552 Site0006 F_0000038 3 2006-02-12 12:28:39.000 2006-02-12 12:28:51.000 Undetermined Unknown Breaker No Damage Undetermined.
3556 Site0006 F_0000038 3 2006-02-12 12:28:39.000 2006-02-12 12:28:51.000 Undetermined Unknown Breaker No Damage Undetermined.
2842 Site0010 F_0000023 1 2006-02-26 14:58:24.000 2006-02-26 14:58:24.000 Other   Recloser   Mylar ballons got across the primary and tripped a recloser on F_0000023 out of Site0010 Substation.
3577 Site0005 F_0000004 2 2006-02-27 22:21:22.000 2006-02-27 22:21:22.000 Tree Unknown Fuse Transformer Tree/Vegetation, XFMR OH, Damaged.
2846 Site0014   7 2006-03-17 11:14:34.000 2006-03-17 11:28:03.000 Equipment   Breaker Load tap changer Bulk Transformer B Load Tap Changer failed at Site0014 Substation causing a bus outage and complete station outage for five minutes and 10 seconds.
21831 Site0002 F_0000044 1 2006-04-18 23:14:23.000 2006-04-18 23:14:23.000         transformer died under t3309
21832 Site0002 F_0000044 1 2006-04-18 23:14:23.000 2006-04-18 23:14:23.000 Lightning       lightning caused this fuse to blow
2850 Site0014   5 2006-04-19 15:01:48.000 2006-04-19 15:01:50.000 Other   Breaker   Smoke from a small brush fire caused a line to line fault, tripping breakers at Substations.
2849 Site0010   5 2006-04-19 15:01:48.000 2006-04-19 15:01:50.000 Other   Breaker   Smoke from a small brush fire caused a line to line fault, tripping breakers at Substations.
21833 Site0002 F_0000046 4 2006-05-05 02:57:19.000 2006-05-05 02:57:19.000 Tree       vines caused this outage under t82
3730 Site0006 F_0000041 1 2006-05-06 14:36:47.000 2006-05-06 14:36:47.000 Equipment Unknown Fuse Other Equipment, Device UG, Damaged.
21834 Site0003 F_0000049 6 2006-05-10 11:47:10.000 2006-05-10 11:47:10.000         bad wind storm primary on ground u
3738 Site0006 F_0000041 1 2006-05-15 02:47:38.000 2006-05-15 02:47:38.000 Equipment Unknown Fuse Cable Equipment, Cable UG, Damaged.
2857 Site0010   7 2006-05-19 14:44:57.000 2006-05-19 14:44:57.000 Lightning Lightning Breaker   Simulteneaus lightning on lines during a lightning storm. Both Substations experienced a temporary interruption of 5 seconds.
2856 Site0014   7 2006-05-19 14:44:57.000 2006-05-19 14:44:57.000 Lightning Lightning Breaker   Simulteneaus lightning on lines during a lightning storm. Both Substations experienced a temporary interruption of 5 seconds.
3740 Site0012 F_0000037 3 2006-05-22 04:31:30.000 2006-05-22 04:31:30.000 Tree Wind Breaker No Damage Tree-Weather-Storm, Device OH, Contact.
3742 Site0012 F_0000037 3 2006-05-22 04:53:56.000 2006-05-22 04:53:56.000 Tree Wind Breaker No Damage Tree-Weather-Storm, Device OH, Contact.
3745 Site0012 F_0000037 3 2006-05-22 05:00:30.000 2006-05-22 05:00:58.000 Tree Wind Breaker No Damage Tree-Weather-Storm, Device OH, Contact.
3746 Site0012 F_0000037 3 2006-05-22 05:00:30.000 2006-05-22 05:00:58.000 Tree Wind Breaker No Damage Tree-Weather-Storm, Device OH, Contact.
3744 Site0012 F_0000037 3 2006-05-22 05:00:30.000 2006-05-22 05:00:58.000 Tree Wind Breaker No Damage Tree-Weather-Storm, Device OH, Contact.
3761 Site0012 F_0000009 3 2006-06-02 04:17:13.000 2006-06-02 04:17:43.000 Equipment Unknown Breaker TEE Equipment, Other Connector UG, Damaged.
3767 Site0012 F_0000009 3 2006-06-02 04:17:13.000 2006-06-02 04:17:43.000 Equipment Unknown Breaker TEE Equipment, Other Connector UG, Damaged.
3762 Site0012 F_0000009 3 2006-06-02 04:17:13.000 2006-06-02 04:17:43.000 Equipment Unknown Breaker TEE Equipment, Other Connector UG, Damaged.
3765 Site0012 F_0000009 3 2006-06-02 04:17:13.000 2006-06-02 04:17:43.000 Equipment Unknown Breaker TEE Equipment, Other Connector UG, Damaged.
3766 Site0012 F_0000009 3 2006-06-02 04:17:13.000 2006-06-02 04:17:43.000 Equipment Unknown Breaker TEE Equipment, Other Connector UG, Damaged.
3776 Site0006 F_0000041 4 2006-06-03 15:27:01.000 2006-06-03 15:27:08.000 Equipment Unknown Sectionalizer Transformer Equipment, XFMR UG, Damaged.
3775 Site0006 F_0000041 4 2006-06-03 15:27:01.000 2006-06-03 15:27:08.000 Equipment Unknown Sectionalizer Transformer Equipment, XFMR UG, Damaged.
3778 Site0006 F_0000041 4 2006-06-03 17:57:41.000 2006-06-03 17:57:41.000 Equipment Unknown Sectionalizer Transformer Equipment, XFMR UG, Damaged.
2861 Site0014 F_0000010 4 2006-06-09 00:36:14.000 2006-06-09 00:36:14.000 Unknown   Recloser   Recloser tripped on F_0000010 no apparent cause.
3816 Site0012 F_0000009 6 2006-06-21 06:06:42.000 2006-06-21 06:06:42.000 Equipment Unknown Fuse Pole Equipment, Pole OH, Down.
21835 Site0003 F_0000049 2 2006-06-21 19:11:36.000 2006-06-21 19:11:36.000         bad transformer under t5063
3843 Site0005   7 2006-06-24 06:37:52.000 2006-06-24 06:37:52.000 Weather Lightning Breaker No Damage Weather Related, Storm, Lightning.
3845 Site0012 F_0000037 7 2006-06-24 07:11:05.000 2006-06-24 07:11:05.000 Weather Lightning Service Restorer No Damage Weather Related, Storm, Lightning.
2867 Site0010   2 2006-06-28 07:17:20.000 2006-06-28 07:17:24.000 Tree   Breaker   A tree contact on Transmission Line caused all the line terminals to trip and reclose.
2868 Site0014   2 2006-06-28 07:17:20.000 2006-06-28 07:17:24.000 Tree   Breaker   A tree contact on Transmission Line caused all the line terminals to trip and reclose.
3894 Site0006 F_0000039 4 2006-06-29 15:46:03.000 2006-06-29 15:46:22.000 Tree Wind Fuse No Damage Tree/Vegetation, Wire OH, Involved.
3893 Site0006 F_0000039 4 2006-06-29 15:46:03.000 2006-06-29 15:46:22.000 Tree Wind Fuse No Damage Tree/Vegetation, Wire OH, Involved.
3895 Site0006 F_0000039 4 2006-06-29 15:46:03.000 2006-06-29 15:46:22.000 Tree Wind Fuse No Damage Tree/Vegetation, Wire OH, Involved.
21836 Site0002 F_0000046 7 2006-07-01 10:57:47.000 2006-07-01 10:57:47.000         service shortng under t2489
21837 Site0002 F_0000046 4 2006-07-01 13:23:19.000 2006-07-01 13:23:19.000         same service still shorting
21838 Site0002 F_0000046 7 2006-07-01 13:33:10.000 2006-07-01 13:33:10.000         service finally smoked
3929 Site0005 F_0000043 1 2006-07-05 05:02:48.000 2006-07-05 05:02:55.000 Equipment Unknown Sectionalizer Cable Equipment, Cable UG, Damaged.
3931 Site0005 F_0000043 1 2006-07-05 05:59:40.000 2006-07-05 05:59:40.000 Equipment Unknown Sectionalizer Cable Equipment, Cable UG, Damaged.
3934 Site0006 F_0000043 5 2006-07-05 09:47:51.000 2006-07-05 09:47:51.000 Equipment Unknown Sectionalizer Cable Equipment, Cable UG, Damaged.
3933 Site0006 F_0000043 5 2006-07-05 09:47:51.000 2006-07-05 09:47:51.000 Equipment Unknown Sectionalizer Cable Equipment, Cable UG, Damaged.
4004 Site0005   3 2006-07-14 11:11:07.000 2006-07-14 11:11:07.000 Unknown Unknown Unknown Unknown Unknown.
4015 Site0011 F_0000007 2 2006-07-15 15:06:46.000 2006-07-15 15:07:30.000 Equipment Unknown Breaker Cable Equipment, Cable UG, Damaged.
4016 Site0011 F_0000007 2 2006-07-15 15:06:46.000 2006-07-15 15:07:30.000 Equipment Unknown Breaker Cable Equipment, Cable UG, Damaged.
4017 Site0011 F_0000007 2 2006-07-15 15:06:46.000 2006-07-15 15:07:30.000 Equipment Unknown Breaker Cable Equipment, Cable UG, Damaged.
21839 Site0002 F_0000046 6 2006-07-16 06:03:01.000 2006-07-16 06:03:01.000         overloaded transformer in a three
21840 Site0002 F_0000044 2 2006-07-18 14:40:36.000 2006-07-18 14:40:36.000 Animal       live bird caused trans fuse to blo
2889 Site0014   2 2006-07-18 19:07:37.000 2006-07-18 19:12:11.000 Tree Lightning Breaker   Transmission Line tripped during a major storm. The cause of this event was likely tree contact. Breakers at Substations tripped and reclosed multiple times.
2884 Site0010   2 2006-07-18 19:07:37.000 2006-07-18 19:12:11.000 Tree Lightning Breaker   Transmission Line tripped during a major storm. The cause of this event was likely tree contact. Breakers at Substations tripped and reclosed multiple times.
2883 Site0014   2 2006-07-18 19:07:37.000 2006-07-18 19:12:11.000 Tree Lightning Breaker   Transmission Line tripped during a major storm. The cause of this event was likely tree contact. Breakers at Substations tripped and reclosed multiple times.
2887 Site0014   2 2006-07-18 19:07:37.000 2006-07-18 19:12:11.000 Tree Lightning Breaker   Transmission Line tripped during a major storm. The cause of this event was likely tree contact. Breakers at Substations tripped and reclosed multiple times.
2880 Site0010   2 2006-07-18 19:07:37.000 2006-07-18 19:12:11.000 Tree Lightning Breaker   Transmission Line tripped during a major storm. The cause of this event was likely tree contact. Breakers at Substations tripped and reclosed multiple times.
2888 Site0010   2 2006-07-18 19:07:37.000 2006-07-18 19:12:11.000 Tree Lightning Breaker   Transmission Line tripped during a major storm. The cause of this event was likely tree contact. Breakers at Substations tripped and reclosed multiple times.
2878 Site0010   2 2006-07-18 19:07:37.000 2006-07-18 19:12:11.000 Tree Lightning Breaker   Transmission Line tripped during a major storm. The cause of this event was likely tree contact. Breakers at Substations tripped and reclosed multiple times.
2879 Site0014   2 2006-07-18 19:07:37.000 2006-07-18 19:12:11.000 Tree Lightning Breaker   Transmission Line tripped during a major storm. The cause of this event was likely tree contact. Breakers at Substations tripped and reclosed multiple times.
2882 Site0010   2 2006-07-18 19:07:37.000 2006-07-18 19:12:11.000 Tree Lightning Breaker   Transmission Line tripped during a major storm. The cause of this event was likely tree contact. Breakers at Substations tripped and reclosed multiple times.
2885 Site0010   2 2006-07-18 19:07:37.000 2006-07-18 19:12:11.000 Tree Lightning Breaker   Transmission Line tripped during a major storm. The cause of this event was likely tree contact. Breakers at Substations tripped and reclosed multiple times.
2881 Site0014   2 2006-07-18 19:07:37.000 2006-07-18 19:12:11.000 Tree Lightning Breaker   Transmission Line tripped during a major storm. The cause of this event was likely tree contact. Breakers at Substations tripped and reclosed multiple times.
2886 Site0014   2 2006-07-18 19:07:37.000 2006-07-18 19:12:11.000 Tree Lightning Breaker   Transmission Line tripped during a major storm. The cause of this event was likely tree contact. Breakers at Substations tripped and reclosed multiple times.
2890 Site0010   4 2006-07-18 19:43:14.000 2006-07-18 19:43:17.000 Lightning Lightning Breaker   Lightning stroke causing several breakers to trip.
2891 Site0014   4 2006-07-18 19:43:14.000 2006-07-18 19:43:17.000 Lightning Lightning Breaker   Lightning stroke causing several breakers to trip.
2892 Site0010   3 2006-07-18 22:49:29.000 2006-07-18 22:49:32.000 Lightning Lightning Breaker   Two Lines tripped simultaneously causing a temporary outage at Bus #1.
2893 Site0014   3 2006-07-18 22:49:29.000 2006-07-18 22:49:32.000 Lightning Lightning Breaker   Two Lines tripped simultaneously causing a temporary outage at Bus #1.
21841 Site0002 F_0000045 7 2006-07-19 13:54:39.000 2006-07-19 13:54:39.000         unknown as to what caused this
4084 Site0005 F_0000038 7 2006-07-23 13:29:45.000 2006-07-23 13:29:45.000 Undetermined Heat Sectionalizer No Damage Undetermined.
4083 Site0006 F_0000038 7 2006-07-23 13:29:45.000 2006-07-23 13:29:45.000 Undetermined Heat Sectionalizer No Damage Undetermined.
4114 Site0012 F_0000036 2 2006-07-25 13:01:58.000 2006-07-25 13:01:58.000 Other Unknown Breaker Cable De-Energized For Safety, Other Connector UG, Contact - Damage.
2899 Site0010 F_0000022 7 2006-07-28 15:54:57.000 2006-07-28 15:54:57.000 Lightning Lightning Breaker   A lightning strike during a major storm caused primary down and tripped the circuit breaker.
2904 Site0014 F_0000016 6 2006-07-28 18:41:06.000 2006-07-28 18:41:06.000 Lightning Lightning Breaker   Lightning during a major storm caused primary wire to fall to the ground and trip the circuit breaker.
21842 Site0002 F_0000044 1 2006-07-30 03:55:07.000 2006-07-30 03:55:07.000 Tree       tree broke primary under n3177
21843 Site0002 F_0000044 2 2006-07-30 14:04:20.000 2006-07-30 14:04:20.000         replace ug elbow under n3395
2907 Site0010 F_0000026 2 2006-08-01 17:07:04.000 2006-08-01 17:08:53.000 Lightning Major Storm Recloser   A lightning strike caused a recloser on F_0000026 to operate twice and caused primary wire to fall to the ground.
2908 Site0010 F_0000026 4 2006-08-01 17:07:04.000 2006-08-01 17:08:53.000 Lightning Major Storm Recloser   A lightning strike caused a recloser on F_0000026 to operate twice and caused primary wire to fall to the ground.
2905 Site0010 F_0000026 2 2006-08-01 17:07:04.000 2006-08-01 17:08:53.000 Lightning Major Storm Recloser   A lightning strike caused a recloser on F_0000026 to operate twice and caused primary wire to fall to the ground.
2906 Site0010 F_0000026 2 2006-08-01 17:07:04.000 2006-08-01 17:08:53.000 Lightning Major Storm Recloser   A lightning strike caused a recloser on F_0000026 to operate twice and caused primary wire to fall to the ground.
2909 Site0010 F_0000024 3 2006-08-01 17:10:37.000 2006-08-01 17:10:37.000 Lightning Major Storm Recloser   A lightning strike caused primary to fall to the ground and trip the circuit breaker of F_0000024.
21844 Site0002 F_0000044 7 2006-08-01 19:13:23.000 2006-08-01 19:13:23.000 Tree       tree brought service down causing
2911 Site0014   2 2006-08-10 13:31:19.000 2006-08-10 13:31:19.000 Unknown   Recloser   No outage information found for this event. May have been a temporary fault cleared by a successful recloser operation per the sag duration.
2912 Site0014   2 2006-08-10 14:25:00.000 2006-08-10 14:25:00.000 Unknown   Recloser   No outage information found for this event. May have been a temporary fault cleared by a successful recloser operation per the sag duration.
2915 Site0014   5 2006-08-13 06:52:37.000 2006-08-13 06:52:38.000 Unknown   Breaker   A fault on Line caused the breaker to trip and reclose. The cause of this event is unknown and it's under investigation.
2914 Site0010   5 2006-08-13 06:52:37.000 2006-08-13 06:52:38.000 Unknown   Breaker   A fault on Line caused the breaker to trip and reclose. The cause of this event is unknown and it's under investigation.
4253 Site0006   7 2006-08-19 05:57:42.000 2006-08-19 05:57:42.000 Unknown Unknown Unknown Unknown Equipment, Cable UG, Damaged.
21845 Site0002 F_0000046 3 2006-08-19 15:38:53.000 2006-08-19 15:38:53.000 Animal       another animal attach under t3537
2918 Site0010 F_0000025 1 2006-08-20 05:40:31.000 2006-08-20 05:40:31.000 Equipment   Breaker   A fault on a Vac Pac Switch in Substation2 caused the circuit breaker of F_0000025 to trip.
2919 Site0010 F_0000023 1 2006-08-20 11:01:38.000 2006-08-20 11:01:38.000 Equipment   Switch   A cable fault in the Substation tripped a Vac Pac Switch. This event is related to the earlier fault that occurred at Substation2
2920 Site0010 F_0000023 1 2006-08-20 18:25:53.000 2006-08-20 18:25:53.000 Equipment   Switch   A cable fault on primary cable feeding Substation2 from F_0000023 tripped a Vac Pac Switch. This event is related to the other two events from Site0010 this same day.
4348 Site0005 F_0000040 7 2006-09-03 13:09:18.000 2006-09-03 13:09:18.000 Undetermined Unknown Breaker No Damage Undetermined.
4373 Site0005 F_0000043 4 2006-09-06 15:26:19.000 2006-09-06 15:26:19.000 Equipment Unknown Fuse Other Equipment, Device UG, Damaged.
21846 Site0002 F_0000044 6 2006-09-07 15:43:37.000 2006-09-07 15:43:37.000 Tree       wind and trees cause this fuse to b
21847 Site0002 F_0000046 7 2006-09-19 10:29:18.000 2006-09-19 10:29:18.000         arcing jumper under t7577
21848 Site0002 F_0000046 7 2006-09-19 10:32:16.000 2006-09-19 10:32:16.000         arching jumper
21849 Site0002 F_0000046 7 2006-09-19 10:34:01.000 2006-09-19 10:34:01.000         arching jumper
21850 Site0002 F_0000046 7 2006-09-19 10:35:45.000 2006-09-19 10:35:45.000         same jumper still arching
21851 Site0002 F_0000046 7 2006-09-19 13:20:13.000 2006-09-19 13:20:13.000         last of srching jumper
21852 Site0002 F_0000044 4 2006-10-01 07:14:05.000 2006-10-01 07:14:05.000         bad switch barrel t6293
2932 Site0014 F_0000018 4 2006-10-03 11:12:09.000 2006-10-03 11:12:09.000 Equipment   Breaker   A splice failure on F_0000018 out of Site0014 caused the circuit breaker to trip.
21853 Site0002 F_0000044 2 2006-10-12 07:30:39.000 2006-10-12 07:30:39.000         unknown grimmlin caused this 10 am
21854 Site0002 F_0000044 7 2006-10-19 16:44:30.000 2006-10-19 16:44:30.000 Tree       bad weather blew down a tree that
21855 Site0002 F_0000044 1 2006-10-30 08:21:57.000 2006-10-30 08:21:57.000         this overload transormer blew under
2940 Site0014 F_0000012 2 2006-10-31 16:33:29.000 2006-10-31 16:33:45.000 Equipment   Recloser   A conductor off the pin on F_0000012 out of Site0014 Sub. caused a recloser to trip.
2942 Site0014 F_0000012 3 2006-10-31 16:33:29.000 2006-10-31 16:33:45.000 Equipment   Recloser   A conductor off the pin on F_0000012 out of Site0014 Sub. caused a recloser to trip.
2941 Site0014 F_0000012 2 2006-10-31 16:33:29.000 2006-10-31 16:33:45.000 Equipment   Recloser Conductor A conductor off the pin on F_0000012 out of Site0014 Sub. caused a recloser to trip.
4513 Site0006 F_0000039 2 2006-11-01 13:23:04.000 2006-11-01 13:23:04.000 Undetermined Unknown Service Restorer No Damage Undetermined.
21856 Site0002 F_0000044 1 2006-11-02 05:03:53.000 2006-11-02 05:03:53.000 Tree       wind and trees caused n3157 to blo
2948 Site0014   4 2006-11-11 01:56:08.000 2006-11-11 01:56:08.000 Unknown   Recloser   Unknown cause. Possible successful recloser operation based on the event duration (4.5 cycles).
2949 Site0010   5 2006-11-14 14:00:43.000 2006-11-14 14:00:46.000 Unknown   Breaker   While attempting to close back in transmission line a fault occurred trippint the a breaker at Substation. This event is under investigation.
2950 Site0014   5 2006-11-14 14:00:43.000 2006-11-14 14:00:46.000 Unknown   Breaker   While attempting to close back in transmission line a fault occurred trippint the a breaker at Substation. This event is under investigation.
21857 Site0002 F_0000044 1 2006-11-25 09:07:38.000 2006-11-25 09:07:38.000         closed transformer cutout
4554 Site0011 F_0000008 1 2006-12-17 01:15:27.000 2006-12-17 01:15:49.000 Equipment Unknown Breaker Connector Equipment, Other Connector UG, Damaged.
4553 Site0011 F_0000008 1 2006-12-17 01:15:27.000 2006-12-17 01:15:49.000 Equipment Unknown Breaker Connector Equipment, Other Connector UG, Damaged.
4552 Site0011 F_0000008 1 2006-12-17 01:15:27.000 2006-12-17 01:15:49.000 Equipment Unknown Breaker Connector Equipment, Other Connector UG, Damaged.
4556 Site0011 F_0000008 1 2006-12-17 03:58:27.000 2006-12-17 03:58:27.000 Equipment Unknown Breaker Connector Equipment, Other Connector UG, Damaged.
2956 Site0014   3 2007-01-02 08:42:48.000 2007-01-02 08:42:48.000 Unknown Wind Breaker   A phase to phase fault on the Transmission Line caused breakers at substations to trip and reclose. The cause of this event is unknown.
2955 Site0010   3 2007-01-02 08:42:48.000 2007-01-02 08:42:48.000 Unknown Wind Breaker   A phase to phase fault on the Transmission Line caused breakers at substations to trip and reclose. The cause of this event is unknown.
21858 Site0002 F_0000044 7 2007-01-18 05:04:05.000 2007-01-18 05:04:05.000         cap bank on
21859 Site0002 F_0000044 4 2007-01-18 05:18:07.000 2007-01-18 05:18:07.000         cap banl off
21860 Site0002 F_0000046 6 2007-01-30 11:06:05.000 2007-01-30 11:06:05.000         t6501 A13808 customers lowside fau
21861 Site0002 F_0000047 6 2007-02-07 11:17:34.000 2007-02-07 11:17:34.000 Vehicle       truck hit pole breaker 1225 33rd s
21862 Site0002 F_0000047 6 2007-02-07 11:18:15.000 2007-02-07 11:18:15.000 Vehicle       truck hit pole 1225 33rd st shot3c
21863 Site0002 F_0000047 7 2007-02-07 11:51:32.000 2007-02-07 11:51:32.000 Vehicle       breaker reclose from truck hiting
21865 Site0002 F_0000047 1 2007-02-07 11:59:03.000 2007-02-07 11:59:03.000         close phase A after pole repair.
21864 Site0002 F_0000047 1 2007-02-07 11:59:03.000 2007-02-07 11:59:03.000 Vehicle       truck hit pole sub breaker 1225 33.
21866 Site0002 F_0000047 2 2007-02-07 11:59:13.000 2007-02-07 11:59:13.000         close another phase.
21867 Site0002 F_0000047 4 2007-02-07 12:00:19.000 2007-02-07 12:00:19.000         close last phase after truck hit p.
21868 Site0003 F_0000050 1 2007-03-22 09:59:08.000 2007-03-22 09:59:08.000         deteriorated line fuse.
21869 Site0002 F_0000047 7 2007-04-13 09:17:28.000 2007-04-13 09:17:28.000 Animal       t3521 100amp woodpecker attack.
21870 Site0002 F_0000047 5 2007-04-13 10:56:27.000 2007-04-13 10:56:27.000         small motor start.
2993 Site0014   1 2007-04-25 17:54:58.000 2007-04-25 17:57:32.000 Unknown   Breaker   A fault on Transmission Line caused breakers at Substations to trip. This event also led to relay overtrips on the other Lines.
2994 Site0010   1 2007-04-25 17:54:58.000 2007-04-25 17:57:32.000 Unknown   Breaker   A fault on Transmission Line caused breakers at Substations to trip. This event also led to relay overtrips on the other Lines.
2995 Site0014   2 2007-04-26 07:08:54.000 2007-04-26 07:08:54.000 Customer Caused   Switch   A fault at a customer switchgear caused a severe voltage sag at the substation bus at Site0014. The fault was cleared by the customer's switchgear.
21871 Site0002 F_0000046 4 2007-05-11 01:41:13.000 2007-05-11 01:41:13.000         T8289 refused trans 10A rabbit att
2997 Site0014 F_0000012 3 2007-05-16 16:15:33.000 2007-05-16 16:15:33.000 Equipment   Breaker   Bad potheads at a riser from F_0000012 out of Site0014 Substation caused the circuit breaker to trip.
2998 Site0014   3 2007-05-16 17:30:50.000 2007-05-16 17:30:50.000 Unknown   Unknown   No outage information found for this event.
2999 Site0014 F_0000017 7 2007-05-18 05:03:45.000 2007-05-18 05:03:45.000 Tree   Breaker   A tree contact on the mainline of F_0000017 from Site0014 Substation tripped the circuit breaker.
21872 Site0002 F_0000044 1 2007-06-25 07:03:37.000 2007-06-25 07:03:37.000         n3157 bad arrester
21873 Site0002 F_0000044 4 2007-07-09 10:49:01.000 2007-07-09 10:49:01.000 Animal       anoher squirrel attack under t6293
21874 Site0002 F_0000044 1 2007-07-25 19:04:52.000 2007-07-25 19:04:52.000         arching
21875 Site0002 F_0000044 4 2007-07-29 14:27:47.000 2007-07-29 14:27:47.000         more arching
21876 Site0002 F_0000044 7 2007-07-29 19:18:07.000 2007-07-29 19:18:07.000         more arching
21877 Site0003 F_0000050 4 2007-07-30 18:28:18.000 2007-07-30 18:28:18.000         t3527 10Amp tree limb.
21878 Site0002 F_0000044 1 2007-07-31 13:18:56.000 2007-07-31 13:18:56.000         last of the arching
21879 Site0002 F_0000047 1 2007-08-30 02:06:38.000 2007-08-30 02:06:38.000         t8937 100amp lightening strike.
21880 Site0002 F_0000047 1 2007-08-30 04:11:34.000 2007-08-30 04:11:34.000         pick up load after lightning strik
21881 Site0002 F_0000044 1 2007-09-29 06:31:55.000 2007-09-29 06:31:55.000